AIC Tables

AIC Tables For C constant

Use these values for C to determine short circuit current in the point-to-point method.

                                             

 

Steel Conduit

Steel Conduit

 

Non-Metallic Conduit

Non-Metallic Conduit

Wire size

Copper Conductor

Aluminum Conductor

Wire Size

Copper Conductor

Aluminum Conductor

AWG #3

4760

2948

AWG #3

4802

2958

AWG #2

5906

3713

AWG #2

6044

3729

AWG #1

7292

4645

AWG #1

7493

4678

AWG # 1/0

8924

5777

AWG # 1/0

9317

5838

AWG # 2/0

10755

7186

AWG #2/0

11423

7301

AWG #3/0

12843

8826

AWG #3/0

13923

9110

AWG #4/0

15082

10740

AWG #4/0

16673

11174

250 kcmil

16483

12122

250 kcmil

18593

12862

300 kcmil

18176

13909

300 kcmil

20867

14922

350 kcmil

19703

15484

350 kcmil

22736

16812

400 kcmil

20565

16670

400 kcmil

24296

18505

500 kcmil

22185

18755

500 kcmil

26706

21390

 